The Regulatory Reform (Fire Safety) Order 2005 requires responsible persons to maintain fire precautions in a suitable state of repair and working order. For fire alarm systems, this means routine testing and planned maintenance at defined intervals. The British Standard BS 5839-1 sets out the specific schedule that most fire risk assessors and enforcement officers will expect you to follow.
This guide explains what that schedule requires, who is responsible for each element, and what happens if it is not followed.
Daily observation
No formal testing is required daily, but BS 5839-1 recommends that the responsible person or a designated member of staff carries out a visual check of the fire alarm control panel. The panel should show normal status with no faults, no activations, and no silenced alerts. This takes under a minute and allows faults to be detected quickly rather than discovered only at the next scheduled test.
Weekly testing
At least one manual call point should be activated each week to verify that the alarm sounder operates. The same call point should not be used consecutively: BS 5839-1 recommends rotating through all call points systematically so that each one is tested regularly over a period of time.
The test should be carried out at the same time each week where practicable, and the result should be recorded in the fire alarm log book. The entry should note the date, the time, the call point used, the name of the person carrying out the test, and whether the system operated correctly.
If the system fails the test, it should be investigated and remedied immediately. A building should not remain occupied with a known fault on the fire alarm system without additional fire precautions in place.
Six-monthly inspection by a competent person
At least every six months, the entire system should be inspected and tested by a competent person. Under BS 5839-1, this means someone with the appropriate training, qualifications and experience to work on fire detection and alarm systems. In practice, this means a contractor holding BAFE SP203-1 certification or equivalent.
The six-monthly inspection typically includes:
- Testing all detection devices (heat detectors, smoke detectors, multi-sensors)
- Testing all manual call points
- Testing all sounders, beacons, and voice alarm outputs
- Checking all cable routes for damage or interference
- Inspecting the control panel and power supplies
- Reviewing the system log book and addressing any outstanding faults
- Issuing a service report documenting findings and any remedial work required
Where a system has more than a certain number of devices, it may be necessary to split inspections between two visits per year rather than attempting a single comprehensive inspection.
Annual review
Once a year, the fire alarm system should be reviewed against the fire risk assessment for the building. Changes to the building’s layout, occupancy or use may affect the suitability of the existing system design. The annual review is an opportunity to ensure the system remains fit for purpose and that the coverage, zoning, and cause-and-effect schedule still reflect how the building operates.
The annual service visit is also the point at which battery backup systems should be tested under load, standby power verified, and the overall system design assessed against any changes in legislation or guidance since the last review.
Reactive maintenance
Any fault indicated on the control panel should be investigated and remedied as soon as practicable. BS 5839-1 defines a fault as a condition that could prevent the system from operating correctly in the event of a fire. A system with an outstanding fault should not be treated as functioning normally: additional fire precautions may be needed while the fault is outstanding.
Common faults include open circuit or short circuit on a detector loop, low battery on a wireless device, a dirty detector triggering a service warning, and control panel power supply faults. Many service contracts include provision for reactive call-outs as part of the annual fee.
The fire alarm log book
BS 5839-1 requires that a log book is kept on site, usually at the fire alarm control panel. The log book is the documentary record of the system’s history and must be available for inspection by the fire authority, your insurer, or any responsible person carrying out a fire audit.
The log book should record every weekly test, every fault and its resolution, every activation (whether genuine or false), every service visit and its findings, and any changes to the system. Without a completed log book, it is difficult to demonstrate compliance even if the physical system is in good order.
Planned preventative maintenance contracts
Most building owners and facilities managers choose to place fire alarm maintenance under a planned preventative maintenance (PPM) contract with a certified contractor. A PPM contract typically covers the scheduled six-monthly inspections, the annual review, reactive call-outs for faults, and reporting. It also gives you a documented audit trail for insurance and regulatory purposes.
When selecting a maintenance contractor, look for BAFE SP203-1 certification. This scheme requires contractors to demonstrate competence in the design, installation, commissioning, and maintenance of fire detection and alarm systems, and is independently audited.
Neuro Systems provides fire alarm maintenance contracts across Nottingham and the East Midlands. We are BAFE certified and work with schools, care homes, commercial premises, and other non-residential buildings. If you are unsure whether your current maintenance schedule meets the requirements of BS 5839-1, contact us for a no-obligation assessment.